Motor Generator Set (MG set)


Motor Generator Set are a combination of an electrical generator and an engine mounted together to form a single piece of equipment. Motor generator set is also referred to as a genset, or more commonly, a generator.

Motor generator sets are used throughout industry to provide electrical power on demand. Typical applications include emergency power backup applications for the medical industry, remote sites, or any industrial or commercial application requiring an independent or remote power source. Motor generator sets are available in most standard power delivery configurations. Power plant installations include gas turbines, diesel and gas reciprocating engines. Motor generator sets may produce alternating current power, or direct current.

Motor generator set can be customized with a wide range of options. These options include a fuel tank, a engine speed regulator and a generator voltage regulator, simple monitoring electrical devices to more advanced digital controls, wireless communication, automatic starting capabilities, and more.


A motor and one or more generators, with their shafts mechanically coupled, used to convert an available power source to another desired frequency or voltage. The motor of the set is selected to operate from the available power supply; the generators are designed to provide the desired output.

The principal advantage of a motor-generator set over other conversion systems is the flexibility offered by the use of separate machines for each function. Since a double energy conversion is involved, electrical to mechanical and back to electrical, the efficiency is lower than in most other conversion methods

Selecting motor generator set for electrical power generation does require a through understanding of power requirements, installation requirements, regulations, and cost attributes. For AC electrical generator sets, specifications will include AC power rating, and for DC specifications will include DC power, expressed in watts (W). Engine-generators are available in a wide range of power ratings. These include small portable units which can supply several hundred watts of power, up to million watt stationary or trailer-mounted units.

Calibrating HART Transmitters

Abstract In order to take advantage of the digital capabilities of HART transmitters, especially for reporting process data values, it is essential that they be calibrated correctly. This paper outlines
the differences between calibrating a conventional and a HART transmitter, and gives recommendations for calibration practices.

Introduction This paper assumes that you want to make use of the digital process values that are available from a HART transmitter. However, before examining calibration requirements, we must first establish a basic understanding in two areas: calibration concepts, and the operation of a HART instrument.

Calibration Concepts The ISA Instrument Calibration Series171 defines calibration as "Determination of the experimental relationship between the quantity being measured and the output of the device which measures it; where the quantity measured is obtained through a recognized standard of measurement." There are two fundamental operations involved in calibrating any instrument:

  • Testing the instrument to determine its performance,
  • Adjusting the instrument to perform within specification
Testing the instrument requires collecting sufficient data to calculate the instrument's operating errors. This is typically accomplished by performing a multiple point test procedure that includes the following steps.

1. Using a process variable simulator that matches the input type of the instrument, set a known input to the instrument.

2. Using an accurate calibrator, read the actual (or reference) value of this input

3 Read the instrument's interpretation of the value by using an accurate calibrator to measure
the instrument output

By repeating this process for a series of different input values, you can collect sufficient data to determine the instrument's accuracy Depending upon the intended calibration goals and the error calculations desired, the test procedure may require from 5 to 2 1 input points The first test that is conducted on an instrument before any adjustments are made is called the As-Found test. If the accuracy calculations from the As-Found data are not within the specifications for the instrument, then it must be adjusted Adjustment is the process of manipulating some part of the instrument so that its input to output relationship is within specification. For conventional instruments, this may be zero and span screws. For HART instruments, this normally requires the use of a communicator to convey specific information to the instrument Often you will see the term calibrate used as a synonym for adjust.

After adjusting the instrument, a second multiple point test is required to characterize the instrument and verify that it is within specification over the defined operating range. This is called the As-Left test It is absolutely essential that the accuracy of the calibration equipment be matched to the instrument being calibrated. Years ago, a safe rule of thumb stated that the calibrator should be an order of magnitude (10 times) more accurate than the instrument being calibrated As the accuracy of field instruments increased, the recommendation dropped to a ratio of 4 to 1. Many common calibrators in use today do not even meet this ratio when compared to the rated accuracy of HART instruments.

Error Calculations
Error calculations are the principal analysis performed on the As-Found and As-Left test data. There are several different types of error calculations, most of which are defined in the publication "Process Instrumentation Terminology ". Al of the ones discussed here are usually expressed in terms of the percent of ideal span which is defined as:

% span =(reading - low range) / (high range - low range) * 100.0

The first step in the data analysis is to convert the engineering unit values for input and output into percent of span Then for each point, calculate the error, which is the deviation of the actual output from the expected output. Table 1 gives a set of example data and error calculations, while Figure 1 graphically illustrates the resulting errors.


It is important to note that the number of data points collected and the order in which they are collected both affect the types of error calculations that can be performed. The maximum error is the most common value used to evaluate an instrument's performance. If a computer program is not used to analyze the test data, it is often the only error considered and is taken to be the largest deviation from the ideal output. A more accurate value can be obtained by fitting an equation to the error data and calculating the maximum and minimum points on the curve. In practice, this should on1 y be done if there are at least five data points reasonably spaced over the instrument range. Otherwise, it is unlikely that the curve fit will give reasonable values between the data points.

By itself, the maximum error does not give a complete indication of an instrument's performance. With the availability of computer software to facilitate calculations, other error values are gaining popularity including zero error, span error, linearity error, and hysteresis error.

Zero error is defined as the error of a device when the input is at the lower range value. Span error is defined as the difference between the actual span and the ideal span, expressed as a percentage of the ideal span.

Linearity error is a measure of how close the error of the instrument over its operating range approaches a straight line. Unfortunately. there are three different methods used to calculate this, resulting in an independent linearity. a terminal based linearity, and a zero based linearity. In practice, it is best to choose one method and apply it consistently. Note that the calculation of linearity error is also greatly facilitated by a curve fit of the error data.

Hysteresis error is a measure of the dependence of the output at a given input value upon the prior history of the input. This is the most difficult error to measure since it requires great care in the collection of data, and it typically requires at least 9 data points to develop reasonable curves for the calculations. Thus a technician must collect at least five data point traversing in one direction, followed by at least four more in the opposite direction, so that each leg has five points, including the inflection point.

If any of these errors is greater than or equal to the desired accuracy for a test, then the instrument has failed and must be adjusted.

Performance over time
In order to adequately assess the long term performance of an instrument, it must be calibrated on a regular schedule You may also want to determine how often an instrument really needs to be calibrated by examining its change in performance over time. To do this, you must collect both As-Found and As-Left data. By comparing the As-Left data from one calibration to the As-
Found of the next calibration. you can determine the instrument's drift. By varying the interval between calibrations, you can determine the optimum calibration interval which allows the instrument to remain within the desired accuracy.


HART Fundamentals
HART is an acronym for Highway Addressable Remote Transducer. Originally developed by Rosemount in 1986, the HART protocol is now a mature, industry-proven technology. Because Rosemount chose to make HART an open protocol, many manufacturers incorporated it into their products. It has now become a de facto standard for field communication with instruments In 1993, to insure its continued growth and acceptance, Rosemount transferred ownership of the protocol to the HART Communication Foundation (HCF).

HART products generally fall into one of three categories: field devices, host systems, and communication support hardware. Field devices include transmitters, valves, and controllers. There are HART transmitters for almost any standard process measurement including pressure,
temperature, level, flow, and analytical (pH. ORP. density). Host systems range from small hand-held communicators to PC based maintenance management software to large scale distributed control systems. Communication support hardware includes simple single loop modems as well as an assortment of multiplexers that allow a host system to communicate with a large number of field devices. In this paper, the general term "communicator" will be used to refer to any HART host that can communicate with a field device.

HART is a transition technology that provides for the continued use of the industry standard 4 - 20 mA current loop while also introducing many of the capabilities and benefits associated with a digital field bus system. The complete technical specification is available from the HART Communication Foundation. HART follows the basic Open Systems Interconnection (OSI) reference model. The OSI model describes the structure and elements of a communication system. The HART protocol uses a reduced OS1 model, implementing only layers 1, 2 and 7. Since the details for layers I (Physical) and 2 (Link) do not directly impact calibration, they are not discussed here. Layer 7, the Application layer, consists of three classes of HART commands: Universal, Common Practice, and Device Specific. Universal commands are implemented by all HART hosts and field devices. They are primarily used by a host to identify a field device and read process data.

The Common Practice command set defines functions that are generally applicable to many field
devices. This includes items such as changing the range, selecting engineering units, and performing self tests. Although each field device implements only those Common Practice commands which are pertinent to its operation, this still provides for a reasonable level of commonality between field devices.
Device Specific commands are different for each field device. It is through these commands that unique calibration and configuration functions are implemented. For example, when configuring an instrument for operation, only temperature transmitters need to be able to change the type of
probe attached, while flow meters often need to have information about pipe sizes, calibration factors, and fluid properties. Also, the calibration procedure for a pressure transmitter isobviously different than that for a valve.

It is important to note that in most cases, proper calibration of a HART instrument requires the
use of a communicator that is capable of issuing device specific commands.

Calibrating a Conventional Instrument
For a conventional 4-20 mA instrument, a multiple point test that stimulates the input and measures the output is sufficient to characterize the overall accuracy of the transmitter. The normal calibration adjustment involves setting only the zero value and the span value, since there is effectively only one adjustable operation between the input and output as illustrated below.

This procedure is often referred to as a Zero and Span Calibration. If the relationship between the input and output range of the instrument is not linear, then you must know the transfer function before you can calculate expected outputs for each input value. Without knowing the expected output values, you cannot calculate the performance errors.

Calibrating a HART Instrument

The Parts of a HART Transmitter
For a HART instrument, a multiple point test between input and output does not provide an accurate representation of the transmitter's operation. Just like a conventional transmitter, the measurement process begins with a technology that converts a physical quantity into an electrical signal. However, the similarity ends there, lnstead of a purely mechanical or electrical path between the input and the resulting 4-20 mA output signal, a HART transmitter has a microprocessor that manipulates the input data. As shown in Figure 4, there are typically three calculation sections involved, and each of these sections may be individually tested and adjusted.

Just prior to the first box, the instrument's microprocessor measures some electrical property that is affected by the process variable of interest. The measured value may be millivolts, capacitance, reluctance, inductance, frequency, or some other property. However, before it can be used by the microprocessor, it must be transformed to a digital count by an analog to digital (AD) converter.

In the first box, the microprocessor must rely upon some form of equation or table to relate the raw count value of the electrical measurement to the actual property (PV) of interest such as temperature, pressure, or flow. The principle form of this table is usually established by the manufacturer, but most HART instruments include commands to perform field adjustments. This is often referred to as a sensor trim. The output of the first box is a digital representation of the process variable. When you read the process variable using a communicator, this is the value that you see.

The second box is strictly a mathematical conversion from the process variable to the equivalent
milliamp representation. The range values of the instrument (related to the zero and span values) are used in conjunction with the transfer function to calculate this value. Although a linear transfer function is the most common, pressure transmitters often have a square root option. Other special instruments may implement common mathematical transformations or user defined break point tables. The output of the second block is a digital representation of the desired instrument output. When you read the loop current using a communicator, this is the value that you see. Many HART instruments support a command which puts the instrument into
a fixed output test mode. This overrides the normal output of the second block and substitutes a specified output value.

The third box is the output section where the calculated output value is converted to a count value that can be loaded into a digital to analog converter. This produces the actual analog electrical signal. Once again the microprocessor must rely on some internal calibration factors to get the output correct. Adjusting these factors is often referred to as a current loop trim or 4- 20 mA trim.

HART Calibration Requirements
Based on this analysis, you can see why a proper calibration procedure for a HART instrument is significantly different than for a conventional instrument. The specific calibration requirements depend upon the application.

If the application uses the digital representation of the process variable for monitoring or control, then the sensor input section must be explicitly tested and adjusted. Note that this reading is completely independent of the milliamp output, and has nothing to do with the zero or span settings. The PV as read via HART communication continues to be accurate even when it is outside the assigned output range. For example, a range 2 Rosemount 305 1 c has sensor limits of -250 to +250 inches of water. If you set the range to 0 - 100 inches of water, and then apply a pressure of 150 inches of water, the analog output will saturate at just above 20 milliamps. However, a communicator can still read the correct pressure. If the current loop output is not used (that is the transmitter is used as a digital only device), then the input section calibration is all that is required. If the application uses the milliamp output, then the output section must be explicitly tested and calibrated. Note that this calibration is independent of the input section, and again, has nothing to do with the zero and span settings.

Calibrating the Input Section
The same basic multiple point test and adjust technique is employed, but with a new definition for output. To run a test, use a calibrator to measure the applied input, but read the associated output (PV) with a communicator. Error calculations are simpler since there is always a linear relationship between the input and output, and both are recorded in the same engineering units. In general, the desired accuracy for this test will be the manufacturer's accuracy specification. If the test does not pass, then follow the manufacturer's recommended procedure for trimming the input section. This may be called a sensor trim and typically involves one or two trim points. Pressure transmitters also often have a zero trim, where the input calculation is adjusted to read exactly zero (not low range). Do not confuse a trim with any form of re-ranging or any procedure that involves using zero and span buttons.

Calibrating the Output Section
Again, the same basic multiple point test and adjust technique is employed, but with a new
definition for input. To run a test, use a communicator to put the transmitter into a fixed current
output mode. The input value for the test is the mA value that you instruct the transmitter to produce. The output value is obtained using a calibrator to measure the resulting current. This test also implies a linear relationship between the input and output, and both are recorded in the same engineering units (milliamps). The desired accuracy for this test should also reflect the manufacturer's accuracy specification.

If the test does not pass, then follow the manufacturer's recommended procedure for trimming the output section. This may be called a 4-20 mA trim, a current loop trim, or a DIA trim. The trim procedure should require two trim points close to or just outside of 4 and 20 mA. Do not confuse this with any form of re-ranging or any procedure that involves using zero and span buttons.

Testing Overall Performance
After calibrating both the Input and Output sections, a HART transmitter should operate correctly The middle block in Figure 4 only involves computations. That is why you can change the range, units, and transfer function without necessarily affecting the calibration. Notice also that even if the instrument has an unusual transfer function, it only operates in the conversion of the input value to a milliamp output value, and therefore is not involved in the testing or calibration of either the input or output sections.

If there is a desire to validate the overall performance of a HART transmitter, run a Zero and Span test just like a conventional instrument. As you will see in a moment. however, passing this test does not necessarily indicate that the transmitter is operating correctly.

Effect of Damping on Test Performance
Many HART instruments support a parameter called damping. If this is not set to zero, it can have an adverse effect on tests and adjustments. Damping induces a delay between a change in the instrument input and the detection of that change in the digital value for the instrument input reading and the corresponding instrument output value. This damping induced delay may exceed the settling time used in the test or calibration. The settling time is the amount of time the test or calibration waits between setting the input and reading the resulting output. It is advisable to adjust the instrument's damping value to zero prior to performing tests or adjustments. After calibration, be sure to return the damping constant to its required value.

Operations that are NOT Proper Calibrations
Digital Range Change
There is a common misconception that changing the range of a HART instrument by using a communicator somehow calibrates the instrument. Remember that a true calibration requires a reference standard, usually in the form of one or more pieces of calibration equipment to provide an input and measure the resulting output. Therefore, since a range change does not reference any external calibration standards, it is really a configuration change, not a calibration. Notice that in the HART transmitter block diagram (Figure 4), changing the range only affects the second block. It has no effect on the digital process variable as read by a communicator.

Zero and Span Adjustment
Using only the zero and span adjustments to calibrate a HART transmitter (the standard practice associated with conventional transmitters) often corrupts the internal digital readings. You may not have noticed this if you never use a communicator to read the range or digital process data. As shown in Figure 4, there is more than one output to consider. The digital PV and milliamp values read by a communicator are also outputs, just like the analog current loop.

Consider what happens when using the external zero and span buttons to adjust a HART instrument. Suppose that an instrument technician installs and tests a differential pressure transmitter that was set at the factory for a range of 0 to 100 inches of water. Testing the transmitter reveals that it now has a 1 inch of water zero shift. Thus with both ports vented (zero), its output is 4.16 mA instead of 4 00 mA, and when applying 100 inches of water, the output is 20.16 mA instead of 20.00 mA. To fix this he vents both ports and presses the zero button on the transmitter. The output goes to 4.00 mA, so it appears that the adjustment was successful
However, if he now checks the transmitter with a communicator, he will find that the range is 1 to 101 inches of water, and the PV is 1 inch of water instead of 0. The zero and span buttons changed the range (the second block). This is the only action that the instrument can take under these conditions since it does not know the actual value of the reference input. Only by using a digital command which conveys the reference value can the instrument make the appropriate internal adjustments.

The proper way to correct a zero shift condition is to use a zero trim. This adjusts the instrument
input block so that the digital PV agrees with the calibration standard. If you intend to use the digital process values for trending, statistical calculations, or maintenance tracking, then you should disable the external zero and span buttons and avoid using them entirely.

Loop Current Adjustment
Another observed practice among instrument technicians is to use a hand-held communicator to adjust the current loop so that an accurate input to the instrument agrees with some display device on the loop. If you are using a Rosemount model 268 communicator, this is a "current loop trim using other scale." Refer again to the zero drift example just before pressing the zero button. Suppose there is also a digital indicator in the loop that displays 0.0 at 4 mA, and 100.0 at 20 mA. During testing, it read 1.0 with both ports vented, and it read 101.0 with 100 inches of water applied. Using the communicator, the technician performs a current loop trim so that the display reads correctly at 0 and 100, essentially correcting the output to be 4 and 20 mA respectively.

While this also appears to be successful, there is a fundamental problem with this procedure. To begin with, the communicator will show that the PV still reads 1 and 101 inches of water at the test points, and the digital reading of the mA output still reads 4.16 and 20.16 mA, even though the actual output is 4 and 20 mA. The calibration problem in the input section has been hidden by introducing a compensating error in the output section, so that neither of the digital readings agrees with the calibration standards.

Conclusion
While there are many benefits to be gained by using HART transmitters, it is essential that they be calibrated using a procedure that is appropriate to their function. If the transmitter is part of an application that retrieves digital process values for monitoring or control, then the standard calibration procedures for conventional instruments are inadequate. At a minimum, the sensor input section of each instrument must be calibrated. If the application also uses the current loop output, then the output section must also be calibrated.

References
[I] HART Communication Foundation. "HART - Smart Communications Protocol Specification",
Revision 5.2, November 3, 1993.
[2] Bell System Technical Reference. PUB 4121 2, "Data Sets 202s and 202T interface
Specification", July 1976.
[3] HART Communication Foundation Pamphlet. "HART Field Communications Protocol".
[4] Holladay, Kenneth L., "Using the HART@ Protocol to Manage for Quality", ISA 1994 paper
number 94-6 17.
[5] Applied System Technologies, Inc., "User's Manual for Cornerstone Base Station", Revision
2.0.1 I , April 1995.
[6] ANSIIISA - S51 .l-1979, "Process Instrumentation Terminology"
[7] Instrument Society of America, "Instrument Calibration Series - Principles of Calibration".
1989.
[8] Instrument Society of America, "Instrument Calibration Series - Calibrating Pressure and
Temperature Instruments", 1989.

HART: The Tutorial

HART® stands for:
HIGHWAY ADDRESSABLE REMOTE TRANSDUCER

HART® is an open protocol that was originally developed in the late 1980's by Fisher Rosemount to communicate with their range of Smart field devices. Over the years it has become a de facto standard for communicating with SMART devices in the Process industry. Over 100 manufacturers utilise the HART® protocol in over 560 different products, from simple temperature transmitters to gas detectors.

The HART® protocol is a powerful communication technology used to realise the full potential of digital field devices whilst preserving the traditional 4-20mA signal. The HART® protocol extends the system capabilities for two way digital communication with smart instruments.


HART® offers the best solution for smart field device communications and has the widest base of support of any field device protocol worldwide. More instruments are available with the HART® protocol than any other digital communications technology. Almost any process application can be addressed by one of the products offered by HART® instrument suppliers. Unlike other digital communication methods the HART protocol gives a unique communication solution that it is backward compatible with currently installed instrumentation. This ensures that investments in existing cabling and current control strategies remain secure into the future.

The HART® digital signal is superimposed onto the standard 4-20mA signal. It uses Bell 202 standard Frequency Shift Keying (FSK) signal to communicate at 1200 baud. The digital signal is made up of two frequencies, 1200Hz and 2200Hz, representing bits 1 and 0 respectively. Sine waves of these two frequencies are superimposed onto the analogue signal cables to give simultaneous analogue and digital communications. As the average value of the FSK signal is always zero there is no effect on the 4-20mA analogue signal. A minimum loop impedance of 230ohms is required for communication.


HART® is a master-slave protocol - this means that a field device only replies when it is spoken to. Up to two masters can connect to each HART® loop. The primary master is usually the DCS (Distributed Control System), the PLC (Programmable Logic Controller) or a PC. The secondary master can be a hand held configurator or another PC running an instrument maintenance software package. Slave devices include transmitters, actuators and controllers that respond to commands from the primary or secondary master.

The digital communication signal has a response time of approx. 2-3 updates per second without interrupting the analogue signal.

HART® Commands
The HART® protocol provides uniform and consistent communication for all field devices via the HART® command set. This includes three types of Command:

Universal

All devices using the HART® protocol must recognise and support these commands. They provide access to information useful in normal operations.

Common Practice

These provide functions implemented by many but not all HART® communication devices.

Device specific

These represent functions that are unique to each field device. They access set up and calibration information as well as information on the construction of the device.

The HART® Communication Protocol is an open standard owned by more than 100 member companies in the HART® Communication Foundation HCF. The HCF is an independent, non-profit organisation, which provides worldwide support for application of the technology and
ensures that the technology is openly available for the benefit of the industry.